Safe practices
If at all possible, shut off the power to a circuit before
performing any work on it. You must secure all sources of harmful
energy before a system may be considered safe to work on. In
industry, securing a circuit, device, or system in this condition is
commonly known as placing it in a Zero Energy State. The
focus of this lesson is, of course, electrical safety. However, many
of these principles apply to non-electrical systems as well.
Securing something in a Zero Energy State means ridding it of any
sort of potential or stored energy, including but not limited to:
- Dangerous voltage
- Spring pressure
- Hydraulic (liquid) pressure
- Pneumatic (air) pressure
- Suspended weight
- Chemical energy (flammable or otherwise reactive substances)
- Nuclear energy (radioactive or fissile substances)
Voltage by its very nature is a manifestation of potential
energy. In the first chapter I even used elevated liquid as an
analogy for the potential energy of voltage, having the capacity
(potential) to produce current (flow), but not necessarily realizing
that potential until a suitable path for flow has been established,
and resistance to flow is overcome. A pair of wires with high
voltage between them do not look or sound dangerous even though they
harbor enough potential energy between them to push deadly amounts
of current through your body. Even though that voltage isn't
presently doing anything, it has the potential to, and that
potential must be neutralized before it is safe to physically
contact those wires.
All properly designed circuits have "disconnect" switch
mechanisms for securing voltage from a circuit. Sometimes these
"disconnects" serve a dual purpose of automatically opening under
excessive current conditions, in which case we call them "circuit
breakers." Other times, the disconnecting switches are strictly
manually-operated devices with no automatic function. In either
case, they are there for your protection and must be used properly.
Please note that the disconnect device should be separate from the
regular switch used to turn the device on and off. It is a safety
switch, to be used only for securing the system in a Zero Energy
State:
With the disconnect switch in the "open" position as shown (no
continuity), the circuit is broken and no current will exist. There
will be zero voltage across the load, and the full voltage of the
source will be dropped across the open contacts of the disconnect
switch. Note how there is no need for a disconnect switch in the
lower conductor of the circuit. Because that side of the circuit is
firmly connected to the earth (ground), it is electrically common
with the earth and is best left that way. For maximum safety of
personnel working on the load of this circuit, a temporary ground
connection could be established on the top side of the load, to
ensure that no voltage could ever be dropped across the load:
With the temporary ground connection in place, both sides of the
load wiring are connected to ground, securing a Zero Energy State at
the load.
Since a ground connection made on both sides of the load is
electrically equivalent to short-circuiting across the load with a
wire, that is another way of accomplishing the same goal of maximum
safety:
Either way, both sides of the load will be electrically common to
the earth, allowing for no voltage (potential energy) between either
side of the load and the ground people stand on. This technique of
temporarily grounding conductors in a de-energized power system is
very common in maintenance work performed on high voltage power
distribution systems.
A further benefit of this precaution is protection against the
possibility of the disconnect switch being closed (turned "on" so
that circuit continuity is established) while people are still
contacting the load. The temporary wire connected across the load
would create a short-circuit when the disconnect switch was closed,
immediately tripping any overcurrent protection devices (circuit
breakers or fuses) in the circuit, which would shut the power off
again. Damage may very well be sustained by the disconnect switch if
this were to happen, but the workers at the load are kept safe.
It would be good to mention at this point that overcurrent
devices are not intended to provide protection against electric
shock. Rather, they exist solely to protect conductors from
overheating due to excessive currents. The temporary shorting wires
just described would indeed cause any overcurrent devices in the
circuit to "trip" if the disconnect switch were to be closed, but
realize that electric shock protection is not the intended function
of those devices. Their primary function would merely be leveraged
for the purpose of worker protection with the shorting wire in
place.
Since it is obviously important to be able to secure any
disconnecting devices in the open (off) position and make sure they
stay that way while work is being done on the circuit, there is need
for a structured safety system to be put into place. Such a system
is commonly used in industry and it is called Lock-out/Tag-out.
A lock-out/tag-out procedure works like this: all individuals
working on a secured circuit have their own personal padlock or
combination lock which they set on the control lever of a disconnect
device prior to working on the system. Additionally, they must fill
out and sign a tag which they hang from their lock describing the
nature and duration of the work they intend to perform on the
system. If there are multiple sources of energy to be "locked out"
(multiple disconnects, both electrical and mechanical energy sources
to be secured, etc.), the worker must use as many of his or her
locks as necessary to secure power from the system before work
begins. This way, the system is maintained in a Zero Energy State
until every last lock is removed from all the disconnect and shutoff
devices, and that means every last worker gives consent by removing
their own personal locks. If the decision is made to re-energize the
system and one person's lock(s) still remain in place after everyone
present removes theirs, the tag(s) will show who that person is and
what it is they're doing.
Even with a good lock-out/tag-out safety program in place, there
is still need for diligence and common-sense precaution. This is
especially true in industrial settings where a multitude of people
may be working on a device or system at once. Some of those people
might not know about proper lock-out/tag-out procedure, or might
know about it but are too complacent to follow it. Don't assume that
everyone has followed the safety rules!
After an electrical system has been locked out and tagged with
your own personal lock, you must then double-check to see if the
voltage really has been secured in a zero state. One way to check is
to see if the machine (or whatever it is that's being worked on)
will start up if the Start switch or button is actuated. If
it starts, then you know you haven't successfully secured the
electrical power from it.
Additionally, you should always check for the presence of
dangerous voltage with a measuring device before actually touching
any conductors in the circuit. To be safest, you should follow this
procedure is checking, using, and then checking your meter:
- Check to see that your meter indicates properly on a known
source of voltage.
- Use your meter to test the locked-out circuit for any
dangerous voltage.
- Check your meter once more on a known source of voltage to see
that it still indicates as it should.
While this may seem excessive or even paranoid, it is a proven
technique for preventing electrical shock. I once had a meter fail
to indicate voltage when it should have while checking a circuit to
see if it was "dead." Had I not used other means to check for the
presence of voltage, I might not be alive today to write this.
There's always the chance that your voltage meter will be defective
just when you need it to check for a dangerous condition. Following
these steps will help ensure that you're never misled into a deadly
situation by a broken meter.
Finally, the electrical worker will arrive at a point in the
safety check procedure where it is deemed safe to actually touch the
conductor(s). Bear in mind that after all of the precautionary steps
have taken, it is still possible (although very unlikely) that a
dangerous voltage may be present. One final precautionary measure to
take at this point is to make momentary contact with the conductor(s) with the back of the hand before grasping it or a metal tool
in contact with it. Why? If, for some reason there is still voltage
present between that conductor and earth ground, finger motion from
the shock reaction (clenching into a fist) will break contact
with the conductor. Please note that this is absolutely the last
step that any electrical worker should ever take before beginning
work on a power system, and should never be used as an
alternative method of checking for dangerous voltage. If you ever
have reason to doubt the trustworthiness of your meter, use another
meter to obtain a "second opinion."
- REVIEW:
- Zero Energy State: When a circuit, device, or system
has been secured so that no potential energy exists to harm
someone working on it.
- Disconnect switch devices must be present in a properly
designed electrical system to allow for convenient readiness of a
Zero Energy State.
- Temporary grounding or shorting wires may be connected to a
load being serviced for extra protection to personnel working on
that load.
- Lock-out/Tag-out works like this: when working on a
system in a Zero Energy State, the worker places a personal
padlock or combination lock on every energy disconnect device
relevant to his or her task on that system. Also, a tag is hung on
every one of those locks describing the nature and duration of the
work to be done, and who is doing it.
- Always verify that a circuit has been secured in a Zero Energy
State with test equipment after "locking it out." Be sure to test
your meter before and after checking the circuit to verify that it
is working properly.
- When the time comes to actually make contact with the
conductor(s) of a supposedly dead power system, do so first with
the back of one hand, so that if a shock should occur, the muscle
reaction will pull the fingers away from the conductor.
|